Vertiv Liebert EXM2, 100-250 kVA/kW (EMEA and APAC)

Vertiv's mid-frame monolithic UPS for EMEA and APAC, declared VFI-SS-111 at 99.2% in eco mode
Vertiv Liebert EXM2, 100-250 kVA/kW (EMEA and APAC) is one of 22 UPS systems tracked in the SecondWatt catalogue, each with specifications, lead times and indicative secondary-market pricing.
Vertiv Liebert EXM2 dossier: 100-250 kVA/kW, VFI-SS-111 declared, 99.2% eco efficiency, EMEA and APAC only, and what a US buyer should look at instead.
Why it matters
That string is a durable, verifiable specification that survives resale, unlike efficiency figures that depend on load point or battery claims that depend on what is in the cabinet. Any UPS dossier that can carry a class code should, and most cannot.
Who buys it
EMEA and APAC data center and enterprise buyers in the 100 to 250 kVA band who want a monolithic machine with a declared VFI-SS-111 class and a lithium-ready battery path. North American buyers should be routed to the Liebert EXM, which is the current product in that market and carries a configure-to-delivery option of four days on the 10 to 40 kVA band.
Role in the data center
Mid-frame primary UPS for EMEA and APAC data halls and enterprise facilities in the 100 to 250 kVA band, with an external VRLA or lithium battery plant.
Key specifications
| Rating range | 100-250 kVA/kW |
|---|---|
| Output power factor | 1.0 (kVA = kW) |
| Double conversion efficiency | up to 97 % |
| Dynamic Online efficiency | 98.8 % |
| Eco mode efficiency | 99.2 % |
| IEC 62040-3 classification | VFI-SS-111 |
| Battery service life | VRLA 3-5 years; lithium-ion 10-15 years |
| Lithium cabinet certification | UL 1973 listed, UL 9540A tested, UL 9540 qualified |
| Region availability | EMEA and APAC only; not listed in the Americas |
| Americas equivalent rating | Liebert EXM 10-200 at 208 V; 30-250 at 480 V kVA/kW |
| Americas equivalent efficiency | 97 double conversion, 99 eco (Liebert EXM) % |
| Americas equivalent delivery | Configure to delivery in 4 days (10-40 kVA, USA) |
Technical summary
Ratings: 100-250 kVA/kW at unity output power factor Efficiency: up to 97% double conversion; 98.8% Dynamic Online; 99.2% eco mode IEC 62040-3 classification: VFI-SS-111, declared by Vertiv Topology: monolithic uninterruptible power supply for mid-size critical applications Battery: lithium-ion ready; VRLA rated 3-5 years against lithium-ion at 10-15 Battery certification: Vertiv lithium-ion cabinets are UL 1973 listed, UL 9540A tested, UL 9540 qualified Region: EMEA and APAC catalogue entries only; absent from the Americas lineup Americas equivalent: Liebert EXM at 10-200 kVA/kW (208 V) and 30-250 kVA/kW (480 V) Liebert EXM efficiency: 97% double conversion and 99% eco mode Liebert EXM delivery: configure-to-delivery in 4 days on 10-40 kVA in the USA
Pricing and availability
Trend: up Warranty, used: 1-year typical from refurbishment dealers.
Lifecycle and maintenance
Static UPS cabinets serve roughly 15 years, the figure Mitsubishi publishes directly alongside a lifecycle-parts-or-replace decision at 10-12 years. The wear items are documented: Eaton rates DC bus capacitors at 7 years of continuous duty and up to 10 under favorable conditions, while Vertiv field data gives 6 years for capacitors and 5-6 years or 40,000-50,000 hours for cooling fans. Batteries turn over far faster, at 3-5 years for sealed VRLA and 12-15 for flooded cells. Service life extension programs rebuild the power train inside the original shell, which is why cabinets routinely outlive their electronics.
Common failure points
- Battery strings — VRLA capacity fades below 80% of nameplate and takes the ride-through with it
- DC bus capacitors — Silent open-circuit loss, or a short that pops and sprays electrolyte across adjacent boards
- Cooling fans — Overheating transfers the load to bypass and leaves it unprotected
- Air filters and dust — Restricted airflow raises internal temperature and shortens capacitor life
- Static bypass switch — Failure to transfer strands the load during maintenance or overload
- Controls obsolescence — Discontinued display and logic boards turn a routine repair into a scavenger hunt
Inspection checklist
Battery age — sealed VRLA turns over at 3-5 years per Eaton lifecycle guidance; assume a full string past that Battery capacity — reject any string below 80% of nameplate capacity under IEEE 1188 practice Battery impedance — ohmic readings above 20% of the commissioning baseline condemn the cell Float voltage — verify 2.23-2.27 VPC at 25 degrees C; float current above 3x steady state flags thermal runaway Intercell connectors — thermal image every joint; a delta above 5 degrees C against neighbors triggers a capacity test DC bus capacitors — Eaton rates 7 years of continuous duty (10 optimal); Vertiv field data gives 6 years at 45,000-50,000 h Cooling fans — Vertiv field data gives 5-6 years or 40,000-50,000 hours; listen for bearing noise at the intake Air filters — pull every filter; a clogged element is the best single proxy for a cabinet that ran above 25 degrees C Load bank test — run 100% and 50% load bank steps; load banking is the de facto acceptance standard in this channel Static bypass — transfer to bypass and back under load 3 times; verify the SCR assembly and breaker interlocks Battery inclusion — get cells, cabinets and racks in writing; a battery package can reach 76% of a 30 kVA class deal Firmware and cards — verify current firmware and a working network card per Eaton's 11-point used-UPS guidance Lifecycle stage — check OEM support status; Mitsubishi's 4-stage table is the only dated public one in the category Documentation — manual, factory startup report and service history; Eaton flags 7-10 year units for capacitor work Removal conditions — verify rigging path, door widths and shutdown window; a 225 kVA cabinet runs 3,605-4,805 lb
Procurement channels
New units through Vertiv's EMEA and APAC channel; product pages are partner-gated. The Americas channel sells the Liebert EXM instead, which one dealer stocks new at 250 kVA without a public price.
Regional notes
EMEA and APAC only, with catalogue entries in EMEA, Asia and India locales. The Canadian URL returns a not-available-for-your-region message, and the US lineup carries Liebert EXM. A US secondary listing for an EXM2 should be treated as a grey import or a mislabeled EXM.